M110

 

Voltage 208 V
Phase 3 Phase
Frequency 50 Hz
Standby 110KVA
Prime 100KVA
Specs
Engine Specification
Engine Model 1104C-44TAG2
Manufacturer PERKINS
Engine Configuration 4 Cylinder in Line
NA or Force Induction Turbo
Bore × Stroke 105 × 127 ( mm )
Displacement 4.4 L
Rated Speed 1500 RPM
Speed Governor Electronic
Starter Model 12V DC Start
Cooling System Water-cooled
Compression Ratio 18.3 : 1
Total Coolant Capacity 17.5 L
Thermostat Open Temperature 82-93℃
Max Coolant Temperature 100℃

 

 

 

Alternator Specifications
Alternator Model TAL-A44-E
Manufacturer LEROY SOMER
Standby Output 110KVA
Excitation Model Brushless, Self-Exciting
Cooling Method Air Cooling
Connection Type 3 Phase and 12 Wires “Star” Connection
Power Factor 0.8 @ 3-phase
Protection Class IP23
Insulation Class H
Altitude ≤1000m
Voltage Regulation, Steady State ≤±1%
Complies with EN 61000-6-3, EN 61000-6-2, EN 55011, group 1 class B for European zone

 

 

 

Fuel System
Fuel Consumption ( Standby Power 100% ) 23.9 L / Hr
Fuel Consumption ( Standby Power 75% ) 18 L /Hr
Fuel Capacity ( L ) 250 L

 

 Dimension & Weight                                                                                                                                           
Model Dimension ( L x W x H ) Inches Weight ( KG ) Noise Level @ 7m dBA
M110 110 x 45 x 62 1500 75

 

 

 


 

WARRANTY

 

Standby-2 Years limited to 500 hours per a year. Prime-One Year

 

Generator set must be serviced quarterly (Standby Applications) or every 250 hours (Prime applications) by authorized dealer.

 

 

 

OEM DEALER CONTACT DETAILS:

 

A.M Electrical Solutions Inc. Bay #1 Gibbons Industrial Park Christ Church, Barbados, Tel:(246) 418-0325

Features

STANDBY RATING

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

 

PRIME RATING

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in12 hours.

 

Standard Features
Main ABB Circuit breaker
One 12V free maintenance battery
Battery Charger
Digital Auto-Start Control Panel with Emergency stop button
Main Battery Cut-off Switch
Exhaust System with Heat Blankets
Residential Grade Silencer
Fuel Level Indicator
Radiator Designed for 50℃ Operating Temp.
Oil Hand Pump for easier Maintenance
Aluminum Canopy Designed for Tropical Environments
Marine Treatment Paint System for Chassis
Stainless Steel Muffler System