M65

 

Voltage 208 V
Phase 3 Phase
Frequency 50 Hz
Standby 65KVA
Prime 58KVA
Specs

Specs & Compare

 

Engine Specification
Engine Model 1104A-44TG1
Manufacturer PERKINS
Engine Configuration 4 Cylinder in Line, 4 Stroker, Direct Injection
NA or Force Induction Turbocharged
Bore × Stroke 105 x 127 ( mm )
Displacement 4.4 L
Rated Speed 1500 RPM
Speed Governor Mechanical
Starter Model 12V DC Start
Cooling System Water-cooled
Compression Ratio 17.25 : 1
Exhaust Gas Flow 7.7 M3/Min
Exhaust Temperature 537 ℃
Max Back Pressure 10 kPa
Max Intake Restriction 6.25 kPa
Burning Capacity 3.1 M3/Min
Air Flow 8180 L/s
Oil Capacity 8.0 L
Oil Consumption ≤0.15% of Fuel Consumption
Oil Pressure at Rated RPM 241-345kPa
Total Coolant Capacity 13.0 L
Thermostat Open Temperature 82-93℃
Max Coolant Temperature 110℃

 

 

 

Alternator Specifications
Alternator Model TAL-A44-H
Manufacturer Leroy Somer
Prime Output 46KVA/58KVA
Standby Output 52KVA/65KVA
Excitation Model Brushless, Self-Exciting
Cooling Method Air Cooling
Connection Type 3- Phase and 12 Wire “Star” Connection
Power Factor 0.8 @ 3-Phase
Protection Class IP23
Insulation Class H
Altitude ≤1000m
Voltage Regulation, Steady State ≤±1%
Telephone Influence Factor <50
Sudden Voltage Warp (100% Sudden Decrease) ≤±1%
Sudden Voltage Warp (Sudden Increase) ≤±25%
Voltage Stable Time (100% Sudden Decrease) ≤6S
Voltage Stable Time (Sudden Increase) ≤6S
Frequency Decrease 0-5% adjustable
Frequency Regulation, Stead State ≤1.5%
Frequency Waving ≤0.8%
Sudden Frequency Warp (100% Sudden Decrease) ≤±12%
Sudden Frequency Warp (100% Sudden Increase) ≤-10%
Frequency Recovery Time (100% Sudden Decrease) ≤55
Frequency Recovery Time (Sudden Increase) ≤55
Compliance GB755,BS5000,VDE0530,NEMAMG1-22,IED34-1,CSA22.2 and AS1359 Stands

 

 

 

 

Fuel System
Fuel Consumption ( Prime Power 100% )/Runtime 14.8 L / 8 hrs
Fuel Consumption ( Prime Power 75% ) 11.2 L / 12.5 hrs
Fuel Capacity ( L ) 135 L

 

 Dimension & Weight                                                                                                             
Model Dimension ( L x W x H ) Inches Weight ( KG ) Noise Level @ 7m dBA
M65-SA 104 x 44 x 60 950 68

 

 

 

 

 

 

WARRANTY

Standby-2 Years limited to 500 hours per a year. Generator set must be serviced quarterly or every 250 hours by authorized dealer Prime- 1 Year . Generator must be serviced every 250 hours by authorized dealer

 

DEALER CONTACT DETAILS:

A.M Electrical Solutions Inc. Bay #1 Gibbons Industrial Park, Christ Church, Barbados, Tel:(246) 418-0325

Features

STANDBY RATING

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

 

PRIME RATING

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in12 hours.

Standard Features
Digital Auto-Start Control Panel with Emergency stop button
Main Circuit breaker
One 12V free maintenance battery
Battery Charger
Battery Security Box
Main Battery Cut-off Switch
Exhaust System with Heat Blankets
Residential Grade Silencer
Extended Bunded Base Tank
Low Level Fuel Alarm
Fuel Level Indicator
Radiator Designed for 50℃ Operating Temp.
Oil Hand Pump for easier Maintenance
Aluminum Canopy Designed for Tropical Environments STAINLESS STEEL Exhaust Mufflers

Marine Paint System on Chassis